ToR3: Building Maintenance & Renovation Works

Safety requirements, materials, and verification in the renovation works

Estimated work: 729 hours across 146 documents · 5,286 pages · see the Work & Effort ledger

How this report was made. Methodology: every document was read and tagged by a large language model (gpt-4.1-mini via the HKBU GenAI gateway) against the Committee's seven Terms of Reference; key points, themes and parties were extracted per document. For each ToR, the relevant documents were grouped into themes and the narratives below were drafted from the documents' own summaries and key points. Inline citations [n] link to this site's HTML rendering of each document (which links to the original PDF on the government site). This page is an editorial aid for journalists and the public; it is not a finding or publication of the Committee, and the original documents remain authoritative.

Overview

The documents reveal significant issues in building maintenance and renovation works at Wang Fuk Court, highlighting irregularities, supervision gaps, and the use of non-compliant materials that contributed to fire safety failures. These deficiencies exacerbated the fire spread and compromised fire service installations and emergency responses.

Report sections by theme

Each section synthesises the relevant documents; inline citations link to each document's page.

Irregularities and Supervision Gaps in Maintenance and Renovation

Multiple documents identify irregularities in building maintenance and renovation works, including unauthorized activities and insufficient supervision. The Hong Kong Police Force’s witness statement highlights unauthorized renovation activities and supervision lapses [54]. Ms. Wong Pik Kiu, a voluntary consultant without formal authority, points to supervision gaps and tender collusion affecting fire safety [2][22]. Additional replies from contractors and companies such as On Cheong Engineering and Mr Mui Siu Fung confirm lack of involvement in decision-making and unclear fire-retardant specifications for materials used [75][76]. These gaps in oversight contributed to compromised building safety and fire service installations.

Cited documents (5)

Use of Non-Compliant and Combustible Materials

The renovation works at Wang Fuk Court involved the use of combustible materials that accelerated fire spread. Foam boards used in renovation lacked clear fire-retardant specifications, as noted in the reply from On Cheong Engineering Limited [76]. The Interim Investigation Report confirms rapid fire spread due to combustible interior materials [55]. Witness statements and supplemental reports further corroborate the role of building materials in exacerbating fire conditions, highlighting a critical failure in material compliance and fire safety standards [28][140].

Cited documents (4)

Failures in Fire Service Installations and Maintenance

The fire service installations at Wang Fuk Court suffered from inadequate maintenance and malfunction during the fire. Multiple witness statements and hearing transcripts describe delayed fire alarm activation, sprinkler system failures, and partial malfunctions of fire service equipment [5][45][85][86][87]. The Closing Address by Counsel for the Committee emphasizes inadequate maintenance of fire service installations as a key factor in the fire spread [45]. The distinction between contractors responsible for renovation and inspection, such as China Status and Victory Fire Engineering, further complicates accountability for maintenance lapses [48][30].

Cited documents (7)

Tender Collusion and Procurement Issues Affecting Maintenance Quality

Tender collusion and procurement irregularities undermined the quality and transparency of building maintenance contracts. The Competition Commission’s reports and addresses highlight anti-competitive practices and bid-rigging risks in fire safety equipment procurement [49][81][63]. Ms. Wong Pik Kiu and Mr Mui Siu Fung’s statements also reference tender collusion and conflicts of interest affecting supervision and contractor selection [2][75]. These procurement issues likely contributed to compromised maintenance standards and fire safety compliance at Wang Fuk Court.

Cited documents (5)

Roles and Responsibilities in Building Maintenance and Fire Safety

The inquiry documents reveal complex roles and responsibilities among owners, management committees, contractors, and government departments regarding building maintenance and fire safety. The 12th Management Committee and Urban Renewal Authority emphasize compliance with regulations but acknowledge challenges in supervision and maintenance [50][61]. Contractors such as Fred & Willie Bros and Hang Fung Building Engineering deny negligence and assert compliance with standards [73][74]. Government bureaus deny negligence and stress interdepartmental coordination in fire safety oversight [46][59]. This diffusion of responsibility contributed to gaps in effective maintenance and fire prevention.

Cited documents (5)

All documents in this ToR (150 (was 113))

Expand each document for its summary, key points and links.

#1 1stletter from Mr TSE Kam Ming to the solicitors of the Independent Committee (English only)7p · 7 img
investigation correspondencewitness statementfire incident commentarylegal communication
  • Mr Tse Kam Ming addresses Independent Committee solicitors
  • Letter contains 7 pages with 7 images
  • Formal communication regarding Wang Fuk Court fire inquiry
  • Details personal or professional perspective on fire incident
#2 1streply from Ms WONG Pik Kiu to the solicitors of the Independent Committee (Chinese only)7p · 7 img
supervision gaptender collusionfire spreadconflict of interest
  • Ms. Wong served as a voluntary consultant for Wang Fuk Court OC.
  • She had no decision-making authority or formal appointment letter.
  • She denied involvement in contractor selection or tender evaluation.
  • No prior relationship with Prestige or its director Hau Wah-kin.
#3 1stSupplemental Witness Statement of Mr LEE Kwok Hung (Chinese only)5p · 26 img
witness testimonyfire investigationevidence supplementationpersonal account
  • Lee Kwok Hung submitted a supplemental witness statement
  • Statement is in Chinese and spans 5 pages
  • Includes 26 extracted images related to the fire
  • Lee is a retired individual providing testimony
#4 1stWitness Statement of Mr CHAN Yat Ho, Matthew13p · 13 img
fire detectionalarm responseevacuationbuilding maintenance
  • Witness is Mr Chan Yat Ho, Matthew
  • Statement covers fire event observations
  • Details on fire detection and alarm response
  • Comments on fire service installations status
#5 1stWitness Statement of Mr CHENG Ka Chun (English only)11p · 11 img
fire ignitionalarm system failureevacuation issuesemergency response
  • Witness observed fire ignition and initial smoke spread
  • Reported delays in fire alarm activation
  • Noted malfunctioning fire service equipment
  • Described evacuation challenges faced by residents
#6 1stWitness Statement of Mr CHUNG Kit Man (Chinese only)9p · 10 img
witness testimonyfire circumstancesinvestigation detailspersonal account
  • Witness statement by Mr Chung Kit Man in Chinese
  • Details personal identification and contact information
  • Provides firsthand account related to Wang Fuk Court fire
  • Includes observations on fire circumstances and response
#8 1stWitness Statement of Mr HO Kin Yip (English only)8p · 8 img
fire timelineevacuationfire safety equipmentcommunication
  • Witness Ho Kin Yip provides first-hand account of fire events
  • Describes timeline and initial fire detection
  • Details evacuation procedures followed
  • Notes condition and functionality of fire safety equipment
#9 1stWitness Statement of Mr KEUNG Sai Ming (English only)47p · 47 img
fire spreadFSI compliancesupervision gaprenovation safety
  • Mr. KEUNG Sai Ming is Assistant Director of FSD since March 2024.
  • Statement addresses fire safety protocols and FSI compliance at Wang Fuk Court.
  • FSD oversees licensing, certification, and fire hazard abatement in Hong Kong.
  • Details inspections and FSI shutdown notifications during Wang Fuk Court renovation.
#11 1stWitness Statement of Mr KU Siu Ping (English only)33p · 33 img
fire detectionevacuation challengesemergency responsecommunication systems
  • Witness Mr Ku Siu Ping provides detailed fire event account
  • Describes initial fire detection and response actions
  • Notes issues with fire alarm and communication systems
  • Mentions building evacuation procedures and challenges
#12 1stWitness Statement of Mr LEUNG Man Chung (Chinese only)4p · 6 img
fire spreadfire responsebuilding safetywitness testimony
  • Witness Leung Man Chung provides first statement on Wang Fuk Court fire
  • Statement submitted to Independent Committee on Wang Fuk Court fire
  • Details personal observations and timeline of fire incident
  • Describes fire spread and response actions
#13 1stWitness Statement of Mr LEUNG Ping Kay (English only)9p · 9 img
fire service shutdownscommunication methodscontractual practicesrenovation coordination
  • Mr. Leung Ping Kay is a director of China Status.
  • China Status contracted with PC&E for Wang Fuk Court fire system shutdowns.
  • SDNs submitted to FSD for 8 buildings' FH/HR systems in Wang Fuk Court.
  • WhatsApp group used for project communications between China Status and PC&E.
#14 1stWitness Statement of Mr LI Man Pong (English only)25p · 1 img
fire alarm delayfire hydrant failureemergency communicationevacuation difficulties
  • Witness Li Man Pong provides detailed fire timeline
  • Observed delayed fire alarm activation
  • Noted malfunctioning fire hydrant system
  • Reported inadequate fire safety training
#15 1stWitness Statement of Mr TANG Wing Wah (English only)23p · 23 img
fire outbreak timelineevacuation proceduresfire equipment statussupervision and coordination
  • Witness is Mr Tang Wing Wah, providing first-hand account
  • Describes fire outbreak timeline and initial response
  • Details on fire alarm activation and evacuation procedures
  • Observations on fire service equipment functionality
#18 1stWitness Statement of Mr WONG Pak Shing (Chinese only)7p · 1 img
building maintenancefire safetywitness testimonycompany responsibility
  • Wong Pak Shing represents Zhipang Industrial Ltd
  • Statement dated March 9, 2026
  • Related to Wang Fuk Court fire inquiry
  • Details personal observations and company role
#20 1stWitness Statement of Mr YEUNG Yan Kin, Andy (English only)11p · 11 img
fire incident timelinefire safety equipmentbuilding maintenanceemergency response
  • Witness statement by Mr Yeung Yan Kin, Andy
  • Details on fire incident timeline and observations
  • Descriptions of fire safety equipment status
  • Comments on building maintenance and repairs
#21 1stWitness Statement of Mr YIU Men Yeung (English only)7p · 7 img
fire originalarm failureevacuation issuesequipment maintenance
  • Witness observed fire origin near electrical panel
  • Reported delayed fire alarm activation
  • Noted absence of sprinkler activation
  • Described evacuation challenges faced by residents
#22 1stWitness Statement of Mr YUE Chak Sang (English only)31p · 31 img
fire spreadfire detectionevacuation proceduresfire equipment functionality
  • Witness Mr Yue Chak Sang provides detailed fire incident account
  • Describes initial fire detection and response actions
  • Notes condition and functionality of fire safety equipment
  • Mentions communication with fire services during incident
#23 1stWitness Statement of Mr YUNG Siu Lun (English only)19p · 19 img
fire spreadevacuationfire safety equipmentbuilding maintenance
  • Witness account of fire outbreak and initial response
  • Describes fire detection and alarm activation timeline
  • Details evacuation procedures and challenges
  • Notes condition and functionality of fire safety equipment
#25 1stWitness Statement of Ms CHENG Tsz Ying (Chinese only)16p · 1 img
witness testimonycompany representationfire inquiry
  • Ms Cheng Tsz Ying submitted first witness statement
  • Represents Zhi Bang Xing Ye Co. Ltd.
  • Statement dated March 9, 2026
  • Related to Wang Fuk Court fire inquiry
#26 1stWitness Statement of Ms LAM Sau Ching (English only)31p · 1 img
fire responseevacuationalarm systembuilding safety
  • Witness account of fire outbreak and initial response
  • Describes evacuation procedures and challenges faced
  • Details on fire alarm activation and communication
  • Observations on fire service arrival and actions
#30 2ndletter from Mr TSE Kam Ming to the solicitors of the Independent Committee (English only)4p · 4 img
investigation processfire safety concernsevidence submissionaccountability
  • Mr Tse Kam Ming submits second letter to Independent Committee solicitors
  • Letter addresses previous inquiries and clarifies statements
  • Provides additional evidence related to fire incident
  • Highlights concerns over investigation process
#31 2ndreply from Ms WONG Pik Kiu to the solicitors of the Independent Committee (Chinese only)9p · 9 img
proxy collectionallegations rebuttalverification processlegal cost accusations
  • Ms. Wong denies allegations of coercion in collecting proxies.
  • Proxies collected via legal street stations, community interactions, and pre-arranged visits.
  • Proxies verified through identity checks and submitted to ISS for validation.
  • Ms. Wong denies paying legal costs for litigants against owner's corporation.
#32 2ndSupplemental Witness Statement of Mr LEE Kwok Hung (Chinese only)7p · 7 img
fire circumstanceswitness testimonyfire service installationsinvestigation process
  • Lee Kwok Hung provides second supplemental witness statement
  • Statement relates to Wang Fuk Court fire investigation
  • Details personal observations and relevant events
  • Includes clarifications on prior testimony
#33 2ndWitness Statement of Mr CHAN Yat Ho, Matthew (Chinese only)5p · 5 img
witness testimonyinvestigation documentationfire inquiry process
  • Second witness statement by Mr. Chan Yat Ho, Matthew
  • Statement related to Wang Fuk Court fire inquiry
  • Provides personal address and identification details
  • Contains five pages and five images
#35 2ndWitness Statement of Mr CHUNG Kit Man (Chinese only)4p · 4 img
fire spreadfire service documentationinspection practicesresponsibility disputes
  • Chung Kit Man submitted a second witness statement on April 3, 2026.
  • Fire occurred at Wang Fuk Court, Tai Po, on November 26, 2025.
  • Chung discussed fire alarm system and inspection issues with Lam Man Yan.
  • Chung provided a link to standard fire service forms during the call.
#36 2ndWitness Statement of Mr FOK Chun Ming (English only)8p · 8 img
fire detectionfire service installationsmaintenance recordsincident communication
  • Mr Fok Chun Ming provided second witness statement
  • Details on fire detection and alarm response
  • Described fire service installation conditions
  • Noted maintenance and inspection records
#37 2ndWitness Statement of Mr HO Kin Yip (English only)9p · 9 img
fire spreadfire service responseevacuation proceduresequipment maintenance
  • Mr Ho Kin Yip provided second witness statement
  • Statement includes detailed fire timeline observations
  • Describes fire spread and smoke conditions
  • Comments on fire service response timing
#40 2ndWitness Statement of Mr KU Siu Ping (English only)15p · 15 img
building materialsinspection findingspublic complaintsresponsibility compliance
  • ICU conducted four site inspections on A/C hoods and architectural features.
  • Foam boards were used in Wang Fuk Court renovation works.
  • Registered Inspector and Contractor are responsible under the Buildings Ordinance.
  • Will Power Architects reported lack of fixing reinforcement in A/C hoods.
#41 2ndWitness Statement of Mr LEUNG Man Chung (Chinese only)3p · 3 img
witness testimonyfire investigationevidence submission
  • Second witness statement by Mr Leung Man Chung
  • Statement related to Wang Fuk Court fire inquiry
  • Document in Chinese, 3 pages with 3 images
  • Submitted to Independent Committee on Wang Fuk fire
#42 2ndWitness Statement of Mr LEUNG Ping Kay (English only)16p · 16 img
fire service procedurescontractor rolesadministrative processescollaboration between RFSICs
  • Mr. Leung Ping Kay supplements his 1st Witness Statement.
  • China Status is a Registered Fire Service Installation Contractor (RFSIC).
  • China Status does not undertake water tank-related works.
  • Mr. Leung is responsible for SDN applications and site inspections.
#49 2ndWitness Statement of Mr YEUNG Yan Kin, Andy (English only)4p · 4 img
fire incident timelinefire safety equipmentemergency responseevacuation challenges
  • Mr Yeung Yan Kin, Andy provided second witness statement
  • Statement focuses on fire incident details at Wang Fuk Court
  • Describes timeline and response actions during fire
  • Highlights issues with fire safety equipment functionality
#51 2ndWitness Statement of Mr YUE Chak Sang (English only)14p · 1 img
fire detectionemergency responseequipment functionalitybuilding evacuation
  • Witness details fire detection and alarm system status
  • Describes response actions taken during fire outbreak
  • Notes issues with fire service installations functionality
  • Highlights communication gaps among emergency responders
#52 2ndWitness Statement of Mr YUNG Siu Lun (English only)11p · 11 img
fire spreadfire service installationsbuilding maintenancesupervision gap
  • Witness account by Mr YUNG Siu Lun on Wang Fuk Court fire
  • Details on fire outbreak and initial response
  • Observations on fire service installations' performance
  • Comments on building maintenance status
#54 2ndWitness Statement of Ms CHENG Tsz Ying (Chinese only)7p · 1 img
witness testimonycompany representationfire inquiry process
  • Ms Cheng Tsz Ying submitted second witness statement
  • Statement dated March 30, 2026
  • Represents Zhipang Industrial Co. Ltd.
  • Related to Wang Fuk Court fire inquiry
#55 2ndWitness Statement of Ms LAM Sau Ching (English only)4p · 1 img
fire detectionevacuationfire service equipmentcommunication gaps
  • Ms Lam Sau Ching provided second witness statement
  • Details on fire detection and alarm response
  • Described evacuation procedures during fire
  • Noted issues with fire service installations
#59 3rdWitness Statement of Mr KEUNG Sai Ming (English only)7p · 1 img
fire detectionevacuation processfire service responsebuilding safety
  • Witness account of fire events at Wang Fuk Court
  • Describes timeline and fire detection response
  • Details on fire alarm activation and evacuation
  • Observations on fire service arrival and actions
#60 3rdWitness Statement of Mr KU Siu Ping (English only)30p · 30 img
fire timelinealarm systemevacuationcommunication
  • Witness Mr Ku Siu Ping provides detailed fire event account
  • Describes timeline and fire detection actions
  • Notes issues with fire alarm responsiveness
  • Mentions evacuation procedures and challenges
#61 3rdWitness Statement of Mr LEUNG Ping Kay (English only)3p · 3 img
fire detectionfire responsecommunication gapsfire safety training
  • Witness Leung Ping Kay provides firsthand fire incident account
  • Describes initial fire detection and response actions
  • Notes delays in fire alarm activation
  • Mentions issues with fire service installations
#62 3rdWitness Statement of Mr LI Man Pong (English only)6p · 6 img
fire timelinefire safety equipmentevacuation procedurescause analysis
  • Witness Mr Li Man Pong provides firsthand account of fire events
  • Describes timeline and initial fire detection
  • Notes condition and response of fire safety equipment
  • Mentions communication with building management
#66 3rdWitness Statement of Mr YIU Men Yeung (English only)3p · 3 img
fire spreadfire safety equipmentevacuationbuilding maintenance
  • Witness account of fire events at Wang Fuk Court
  • Observed timeline and fire spread details
  • Noted condition of fire safety equipment
  • Described evacuation procedures followed
#69 4thWitness Statement of Mr YIU Men Yeung (English only)27p · 27 img
fire spreadtenability assessmentevacuation safetyfirefighting impact
  • Mr. YIU Men Yeung provided his 4th witness statement to the Committee.
  • Statement addresses Questions 11-14 from the Committee's 2 March Letter.
  • Fire spread rapidly through re-entrants, worsening untenable conditions in common areas.
  • Dynamic fire progression hindered precise assessment of tenability in affected areas.
#74 Closing Address by Counsel for ISS EastPoint Properties Limited (English only)28p · ? img
liability disputefire safety compliancemaintenance recordscausation debate
  • ISS EastPoint denies liability for fire spread
  • Argues compliance with fire safety regulations
  • Challenges adequacy of fire service installations
  • Highlights maintenance records and inspections
#75 Closing Address by Counsel for Mr LEUNG Ping Kay (English only)20p · ? img
legal defenseevidence scrutinyaccountabilityinvestigation fairness
  • Defense emphasizes lack of direct causation by Mr Leung
  • Challenges reliability of prosecution evidence
  • Highlights procedural fairness and legal standards
  • Argues no negligence proven against Mr Leung
#76 Closing Address by Counsel for nine Wang Fuk Court residents (Chinese only)25p · ? img
fire safety failuresbuilding maintenanceaccountabilityinvestigation transparency
  • Nine Wang Fuk Court residents jointly submit closing address
  • Residents highlight fire safety system failures
  • Call for accountability of building management
  • Emphasis on inadequate maintenance and supervision
#77 Closing Address by Counsel for the Committee (English only)627p · 128 img
fire spreadsprinkler failuresupervision gapbuilding maintenance
  • Fire caused by multiple safety system failures
  • Inadequate maintenance of fire service installations
  • Lapses in supervision and enforcement identified
  • Building renovation works contributed to fire spread
#78 Closing Address by Counsel for the Relevant Bureaux and Departments of the Government (English only)408p · ? img
fire safety compliancegovernment accountabilityinter-department coordinationbuilding maintenance
  • Government bureaus deny negligence in fire prevention
  • Emphasize compliance with existing fire safety regulations
  • Highlight coordination among departments during fire response
  • Argue adequacy of building maintenance and inspections
#79 Closing Address by Counsel for Urban Renewal Authority (Chinese only)9p · ? img
building maintenancesupervision rolesfire safety compliancerenovation works
  • URA denies responsibility for fire cause
  • Emphasizes compliance with building regulations
  • Highlights maintenance and inspection records
  • Refutes claims of negligence in renovation works
#80 Closing Address by Counsel for Victory Fire Engineering Limited (English only)19p · 19 img
fire service rolesregulatory frameworknotification dutieslegislative gaps
  • Victory Fire was RFSIC for annual inspections, not renovation works.
  • China Status was RFSIC for renovation works at Wang Fuk Court.
  • ISS Eastpoint Properties managed Wang Fuk Court during the incident.
  • Victory Fire argues no duty to notify FSD of FAS shutdown.
#81 Closing Address by Representative of Competition Commission (English only)13p · ? img
tender collusionprocurement transparencymarket oversightanti-competitive practices
  • Competition Commission highlights anti-competitive practices risks
  • Emphasizes need for fair tendering in building maintenance
  • Warns against collusion and bid-rigging in contracts
  • Calls for stronger oversight to prevent market abuses
#82 Closing Address by the 12th Management Committee of the Incorporated Owners of Wang Fuk Court (Chinese only)10p · ? img
fire safety improvementbuilding maintenanceowner managementinquiry support
  • Second Management Committee expresses heartfelt thanks
  • Acknowledges challenges faced during fire aftermath
  • Calls for improved fire safety measures
  • Highlights need for better building maintenance
#83 Directions of the Chairman of the Independent Committee made at the hearing on 8 May 20263p · ? img
inquiry proceduresevidence managementtransparencyconfidentiality
  • Chairman issued procedural directions at 8 May 2026 hearing
  • Focus on evidence submission deadlines and witness testimonies
  • Clarification on scope of inquiry topics and document disclosures
  • Emphasis on transparency and timely cooperation from parties
#84 Expert Report by Professor Asif Sohail USMANI and Professor JIANG Liming, Fire Engineering Experts appointed by the Independent Committee (English onl130p · 115 img
fire spreadsprinkler failuresmoke controlbuilding fire resistance
  • Fire spread accelerated by compartmentation failures
  • Sprinkler system coverage was incomplete and ineffective
  • Smoke control systems did not perform as designed
  • Fire resistance of key structural elements was inadequate
#85 Final Investigation Report of the Inter-departmental Fire Investigation Task Force (Appendix A-27 is the Expert Report by Professor YUEN Kwok Kit, Ric1142p · 4558 img
fire originfire spreadfire safety installationsbuilding design
  • Expert report by Prof. Yuen Kwok Kit on fire engineering
  • Detailed analysis of fire origin and spread
  • Assessment of fire safety installations effectiveness
  • Evaluation of building materials and design impact
#112 Hong Kong Police Force’s witness statement on irregularities in building maintenance and renovation works (English only)15p · 14 img
building maintenancerenovation irregularitiessupervision gapcontractor certification
  • Police identify irregularities in building maintenance works
  • Evidence of unauthorized renovation activities found
  • Maintenance records show discrepancies and falsifications
  • Contractors involved lacked proper certification
#113 Interim Investigation Report of the Inter-departmental Fire Investigation Task Force (English only)113p · 191 img
fire originfire spreadfire service equipmentsupervision gap
  • Fire originated in a residential unit at Wang Fuk Court
  • Rapid fire spread due to combustible interior materials
  • Fire service installations partially functional but insufficient
  • Delayed evacuation contributed to casualties
#116 List of Involved Parties (as at 23 April 2026)3p · ? img
involved partiesroles and responsibilitiesaccountabilityfire safety management
  • Comprehensive list of parties involved in Wang Fuk Court fire inquiry
  • Includes government departments and contractors
  • Details roles and responsibilities of each party
  • Covers fire safety and building maintenance entities
#127 Opening Address by Counsel for Hop On Management Company Limited (Chinese only)4p · ? img
building maintenancesupervision rolesfire preventionmanagement responsibility
  • Hop On Management defends its fire safety management role
  • Emphasizes compliance with building maintenance regulations
  • Challenges allegations of negligence in fire prevention
  • Highlights limitations in control over residents' actions
#128 Opening Address by Counsel for ISS EastPoint Properties Limited (English only)19p · ? img
supervision gapbuilding maintenanceroles and responsibilitiesfire safety compliance
  • ISS EastPoint Properties Limited represented by counsel
  • Opening address outlines company’s position on fire incident
  • Emphasis on compliance with fire safety regulations
  • Denial of negligence in building maintenance
#129 Opening Address by Counsel for Relevant Bureaux and Departments of the Government28p · ? img
government responsefire safety regulationsinterdepartmental coordinationbuilding maintenance
  • Government bureaus emphasize coordinated response to fire
  • Acknowledgement of existing fire safety regulations
  • Commitment to transparent inquiry process
  • Highlight roles of various departments in fire management
#130 Opening Address by Counsel for the Committee20p · ? img
fire investigationsupervision gapsystemic issueslegal adequacy
  • Committee established to investigate Wang Fuk Court fire
  • Focus on causes, fire service installations, and maintenance
  • Examination of supervision and roles of involved parties
  • Assessment of systemic issues including collusion risks
#131 Opening Address by Counsel for Urban Renewal Authority (English only)115p · 14 img
building maintenancesupervision gapfire service coordinationsystemic improvements
  • URA emphasizes commitment to fire safety in redevelopment projects
  • Acknowledges challenges in building maintenance and renovation
  • Highlights coordination with fire services and regulatory bodies
  • Stresses importance of clear roles and responsibilities
#132 Opening Address by Mr Tsui Moon Come, Tony, Chairperson of the 12th Management Committee of the Incorporated Owners of Wang Fuk Court (Chinese only)3p · ? img
fire safety awarenessinvestigation transparencyresident concernsbuilding safety
  • Chairperson introduces 12th Management Committee role
  • Emphasizes importance of fire safety awareness
  • Calls for transparent investigation process
  • Highlights residents' concerns on fire prevention
#133 Opening Address by Representative of Competition Commission (English only)90p · 13 img
tender collusionprocurement transparencyfire safety complianceregulatory oversight
  • Competition Commission highlights importance of fair tendering
  • Emphasizes risks of bid-rigging in building maintenance contracts
  • Calls for transparency in procurement processes
  • Warns against collusion affecting fire safety standards
#135 Presentation Slides by Dr LEE Wing Man (English only)40p · 62 img
fire spreadfire service installationsbuilding maintenancesupervision gaps
  • Detailed analysis of fire causes and spread mechanisms
  • Assessment of fire service installations performance
  • Evaluation of building maintenance and renovation impact
  • Identification of supervision and responsibility gaps
#136 Presentation Slides by Dr TO Chi Wing (English only)41p · 891 img
fire spreadfire service installationsbuilding maintenancefire safety management
  • Fire origin and initial spread analysis presented
  • Evaluation of fire service installations effectiveness
  • Assessment of building materials and fire resistance
  • Identification of maintenance issues affecting fire safety
#137 Presentation Slides by Mr LAM Kin Kwan (English only)20p · 500 img
fire spreadfire service installationsbuilding maintenancesupervision gap
  • Deputy Leader of IFITF presented key fire investigation findings
  • Analysis of fire spread and contributing factors
  • Assessment of fire service installations effectiveness
  • Identification of building maintenance issues
#139 Presentation Slides by Professor Asif Sohail USMANI and Professor JIANG Liming (English only)83p · 75 img
fire spreadsprinkler failurebuilding designevacuation safety
  • Fire spread influenced by building design and ventilation
  • Sprinkler system coverage was incomplete in Wang Fuk Court
  • Fire resistance of materials was below recommended standards
  • Evacuation routes were partially obstructed during fire
#140 Presentation Slides by Professor YUEN Kwok Kit, Richard (English only)49p · 462 img
fire spreadfire service installationsbuilding designsupervision gap
  • Detailed fire engineering analysis of Wang Fuk Court fire
  • Identified fire spread mechanisms and contributing factors
  • Assessment of fire service installations and their performance
  • Evaluation of building design and materials in fire context
#142 Recommendations by Professor Asif Sohail USMANI and Professor JIANG Liming, Fire Engineering Experts appointed by the Independent Committee (English o4p · ? img
fire safety improvementssprinkler system enhancementfire detection upgradesregulatory recommendations
  • Fire engineering experts provide detailed safety recommendations
  • Emphasis on improving fire detection and alarm systems
  • Recommendations include enhanced sprinkler system coverage
  • Focus on building design to prevent fire spread
#144 Recommendations on improvement measures by nine Wang Fuk Court residents concerning Terms of Reference (1) and (2) of Independent Committee (Chinese o9p · ? img
fire causesfire service installationsresident recommendationsfire safety improvements
  • Nine Wang Fuk Court residents submitted improvement recommendations
  • Recommendations focus on Terms of Reference 1 and 2
  • Emphasis on fire causes and fire service installations
  • Residents highlight need for better fire detection systems
#145 Recommendations on improvement measures by the Government concerning Terms of Reference (1) and (2) of Independent Committee (English only)34p · ? img
fire service installationsregulatory improvementmaintenance protocolspublic safety awareness
  • Government proposes enhanced fire safety regulations
  • Improvement of fire service installations recommended
  • Stricter maintenance protocols for fire equipment
  • Upgrading sprinkler and alarm systems suggested
#146 Reply from Lam Kee Construction Materials (Chinese only)5p · 4 img
delivery logisticsorder processingmaterial supplycommunication clarity
  • Lam Kee handles order taking and delivery arrangements
  • Two staff members responsible for orders and deliveries
  • Ying Lee Fung company ordered protective nets
  • Lam Kee unaware of specific use of delivered materials
#147 Reply from Messrs. King & Company (Acting for Fred & Willie Bros Const Eng Co Limited) (English only)8p · 8 img
building maintenancefire service installationssupervisionliability dispute
  • Fred & Willie Bros deny negligence in fire-related works
  • Company asserts compliance with building and fire safety standards
  • Disputes allegations of faulty installation of fire equipment
  • Claims all renovation works were supervised and approved
#148 Reply from Messrs. Wong & Lawyers (Acting for Hang Fung Building Engineering Limited) (Chinese only)8p · 8 img
legal defensecompany responsibilitybuilding maintenanceregulatory compliance
  • Hang Fung Building Engineering Limited responds to inquiry
  • Legal representation by Messrs. Wong & Lawyers
  • Denial of liability for fire-related claims
  • Details on company’s role in building works
#150 Reply from Mr MUI Siu Fung to the solicitors of the Independent Committee (Chinese only)5p · 5 img
supervision gaptender collusionconflict of interestproxy vote allegations
  • Mr. Mui attended meetings as a guest, not involved in decisions.
  • No participation in contractor selection, budgeting, or project oversight.
  • Assisted in finding venues for special meetings, not renovation discussions.
  • Denied allegations of proxy vote manipulation or conflicts of interest.
#152 Reply from On Cheong Engineering Limited (Chinese only)8p · 8 img
fire spreadmaterial compliancesupervision gapworker safety
  • On Cheong handled external wall repairs for Wang Fuk Court renovation.
  • Foam boards used to protect windows lacked clear fire-retardant specifications.
  • Committee seeks details on foam board procurement and fire safety compliance.
  • Subcontractor's role in altering fire-rated stairwell windows questioned.
#153 Reply from Red Sun Construct (Asia) Engineering Limited (Chinese only)6p · 6 img
building maintenancerenovation worksresponsibility clarificationworkmanship quality
  • Red Sun Construct responded to inquiry on Wang Fuk Court fire
  • Provided detailed explanations on construction and maintenance works
  • Addressed allegations regarding workmanship and safety compliance
  • Clarified roles and responsibilities during renovation
#154 Reply from the Development Bureau (English only)6p · ? img
building maintenancesupervision rolesfire safety complianceinter-agency coordination
  • Development Bureau responded to Independent Committee's request
  • Provided clarifications on building maintenance policies
  • Outlined roles in supervision and enforcement
  • Addressed compliance with fire safety regulations
#155 Reply from Tin Hung Engineering Company (Chinese only)7p · 5 img
building maintenancefire safety equipmentsubcontractor rolecompliance
  • Tin Hung Engineering responded regarding Wang Fuk Court maintenance
  • Company acted as subcontractor for repair works
  • Clarified scope and timeline of their maintenance tasks
  • Addressed queries on fire safety equipment servicing
#156 Reply from王華添工程公司(Chinese only)6p · 6 img
company responseengineering rolefire incident inquirydocumentation
  • 王華添工程公司提交正式回覆文件
  • 回應涉及火災相關工程問題
  • 提供公司聯絡及地址資訊
  • 文件包含6頁及6張圖片
#157 Report of Competition Commission concerning Terms of Reference (2) of Independent Committee (English only)91p · 13 img
tender collusionprocurement irregularitiesfire safety equipmentregulatory oversight
  • Competition Commission investigated tendering irregularities
  • Evidence of bid-rigging in fire safety equipment contracts
  • Collusion among contractors identified
  • Recommendations to enhance procurement transparency
#158 Report of Independent Commission Against Corruption concerning Terms of Reference (2) of Independent Committee (English only)63p · 15 img
corruption investigationfire service equipmentprocurement irregularitiesoversight failures
  • ICAC investigated corruption related to fire safety installations
  • Focus on Terms of Reference (2) concerning fire service equipment
  • Evidence of irregularities in procurement and installation processes
  • Findings highlight potential conflicts of interest and bribery
#159 Response of the 12th Management Committee of the Incorporated Owners of Wang Fuk Court for the term from 6 September 2024 to 6 January 2026 in relatio31p · ? img
building maintenancerenovation worksresident communicationfire safety
  • 12th Management Committee term from Sept 2024 to Jan 2026
  • Response addresses Wang Fuk Court and major repair works
  • Committee outlines maintenance and renovation efforts
  • Highlights communication with residents and stakeholders
#161 Synopsis of Closing Address by Counsel for the Relevant Bureaux and Departments of the Government (Chinese only)24p · ? img
supervision gapfire service installationsbuilding maintenanceregulatory adequacy
  • Government bureaux and departments present closing address summary
  • Focus on roles and responsibilities in fire prevention
  • Emphasis on existing fire safety regulations compliance
  • Discussion on adequacy of fire service installations
#162 Transcript of Evidential Hearing held on 1 April 2026 (Draft)43p · ? img
fire spreadsprinkler failuresupervision gapmaintenance issues
  • Witnesses detailed timeline of fire outbreak and response
  • Fire service installations partially malfunctioned during incident
  • Maintenance records showed delayed repairs on key equipment
  • Supervisory roles during fire response were unclear
#163 Transcript of Evidential Hearing held on 10 April 2026 (Draft)47p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses detailed timeline of fire outbreak and response
  • Fire service installations reportedly malfunctioned during fire
  • Maintenance records for Wang Fuk Court were incomplete
  • Supervisory roles during fire response were unclear
#164 Transcript of Evidential Hearing held on 13 April 2026 (Draft)32p · ? img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witnesses testified on fire origin and spread timeline
  • Discussions on malfunctioning fire alarms and sprinklers
  • Maintenance records showed irregular inspections
  • Conflicting accounts on emergency response effectiveness
#165 Transcript of Evidential Hearing held on 15 April 2026 (Draft)40p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses testified on fire origin and spread
  • Discussion on malfunction of fire alarms and sprinklers
  • Maintenance records for Wang Fuk Court reviewed
  • Responsibility of building management questioned
#166 Transcript of Evidential Hearing held on 15 July 2026 (Draft)14p · ? img
fire spreadsprinkler failuremaintenance lapsesresponse coordination
  • Witnesses detailed fire outbreak timeline
  • Fire alarms activated late during incident
  • Sprinkler system malfunction reported
  • Maintenance records showed irregular inspections
#167 Transcript of Evidential Hearing held on 16 April 2026 (Draft)30p · 1 img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussions on malfunctioning fire alarms and sprinklers
  • Debate over adequacy of building maintenance records
  • Conflicting testimonies on emergency response effectiveness
#168 Transcript of Evidential Hearing held on 16 July 2026 (Draft)29p · ? img
fire spreadsprinkler failuresupervision gapevacuation delay
  • Witnesses detailed timeline of fire outbreak and response
  • Discussion on malfunction of fire alarms and sprinklers
  • Maintenance records for fire safety equipment reviewed
  • Roles of building management and fire services scrutinized
#169 Transcript of Evidential Hearing held on 17 April 2026 (Draft)37p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on malfunctioning fire alarms and sprinklers
  • Maintenance records for fire safety equipment were incomplete
  • Responsibility for building safety oversight debated
#170 Transcript of Evidential Hearing held on 17 July 2026 (Draft)29p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on malfunctioning fire alarms and sprinkler systems
  • Maintenance records for fire safety equipment were incomplete
  • Responsibility of property management company questioned
#171 Transcript of Evidential Hearing held on 19 March 2026 (Draft)32p · ? img
fire spreadsprinkler failuresupervision gapemergency response
  • Witnesses detailed timeline of fire outbreak and response
  • Issues raised about malfunctioning fire alarms and sprinklers
  • Delays in fire brigade arrival noted
  • Maintenance records for fire equipment were incomplete
#172 Transcript of Evidential Hearing held on 2 April 2026 (Draft)36p · ? img
fire spreadfire service equipmentbuilding maintenancesupervision gap
  • Witnesses detailed fire outbreak timeline and initial response
  • Fire service equipment functionality discussed
  • Maintenance records of Wang Fuk Court reviewed
  • Roles of building management and fire services examined
#173 Transcript of Evidential Hearing held on 20 April 2026 (Draft)22p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on malfunctioning fire alarms and sprinklers
  • Maintenance records showed irregular inspection intervals
  • Responsibility of building management questioned
#174 Transcript of Evidential Hearing held on 20 March 2026 (Draft)26p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses detailed timeline of fire outbreak and response
  • Discussion on malfunctioning fire alarms and sprinklers
  • Maintenance records showed irregular inspections
  • Responsibility of building management questioned
#175 Transcript of Evidential Hearing held on 21 April 2026 (Draft)28p · ? img
fire spreadfire service installationsbuilding maintenancesupervision roles
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussions on fire alarm system performance and failures
  • Examination of building evacuation procedures
  • Testimonies on maintenance records and renovation works
#176 Transcript of Evidential Hearing held on 22 April 2026 (Draft)27p · ? img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witness testimonies on fire origin and spread
  • Discussion on fire alarm and sprinkler activation
  • Examination of building maintenance records
  • Clarification of roles of fire safety officers
#177 Transcript of Evidential Hearing held on 22 June 2026 (Draft)127p · ? img
fire spreadsprinkler failuresupervision gapemergency response
  • Witness testimonies detail fire outbreak timeline
  • Discussions on fire alarm and sprinkler activation
  • Maintenance records of fire safety equipment reviewed
  • Roles of building management and fire services examined
#178 Transcript of Evidential Hearing held on 23 April 2026 (Draft)23p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses testified on fire origin and spread timeline
  • Discussions on malfunctioning fire alarms and sprinklers
  • Maintenance records for fire safety equipment reviewed
  • Responsibility of building management questioned
#179 Transcript of Evidential Hearing held on 24 April 2026 (Draft)29p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on malfunctioning fire alarms and sprinklers
  • Maintenance records for fire safety equipment were incomplete
  • Responsibility of building management in safety oversight debated
#180 Transcript of Evidential Hearing held on 24 June 2026 (Draft)24p · ? img
fire spreadfire service installationsbuilding maintenancesupervision gap
  • Witnesses detailed timeline of fire outbreak and response
  • Fire service installations' performance discussed
  • Maintenance records of Wang Fuk Court scrutinized
  • Roles of building management and fire services examined
#181 Transcript of Evidential Hearing held on 24 March 2026 (Draft)27p · ? img
fire spreadsprinkler failuresupervision gapemergency response
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on functionality of fire alarms and sprinklers
  • Maintenance records of fire safety equipment reviewed
  • Roles of building management and fire services examined
#182 Transcript of Evidential Hearing held on 25 June 2026 (Draft)27p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussions on malfunctioning fire alarms and sprinklers
  • Debate over adequacy of building maintenance records
  • Conflicting testimonies on emergency response times
#183 Transcript of Evidential Hearing held on 26 March 2026 (Draft)27p · ? img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussions on malfunctioning fire alarms and sprinkler systems
  • Debate over adequacy of building maintenance records
  • Clarifications on roles of property management and fire services
#184 Transcript of Evidential Hearing held on 27 April 2026 (Draft)35p · ? img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witnesses testified on fire origin and spread
  • Discussion on malfunction of fire alarms and sprinklers
  • Maintenance records of Wang Fuk Court scrutinized
  • Roles of building management and fire services examined
#185 Transcript of Evidential Hearing held on 30 April 2026 (Draft)37p · ? img
fire spreadsprinkler failuresupervision gapbuilding maintenance
  • Witnesses described rapid fire spread in Wang Fuk Court
  • Fire alarms activated but sprinkler system failed to operate
  • Maintenance records showed delayed repairs on fire equipment
  • Conflicting testimonies on supervision roles during renovation
#186 Transcript of Evidential Hearing held on 30 March 2026 (Draft)36p · ? img
fire spreadfire service installationsbuilding maintenancesupervision roles
  • Witness testimonies on fire origin and spread
  • Discussions on fire safety equipment functionality
  • Examination of building maintenance records
  • Clarifications on roles of fire safety officers
#187 Transcript of Evidential Hearing held on 31 March 2026 (Draft)39p · ? img
fire spreadsprinkler failurebuilding maintenancesupervision gap
  • Witnesses detailed fire outbreak timeline and initial response
  • Discussions on fire alarm system functionality and failures
  • Testimonies on maintenance records and renovation works
  • Clarifications on roles of fire services and building management
#188 Transcript of Evidential Hearing held on 6 May 2026 (Draft)43p · ? img
fire spreadfire service installationsbuilding maintenancesupervision gap
  • Witnesses provided detailed accounts of fire outbreak and response
  • Discussions on adequacy of fire service installations
  • Evidence on building maintenance and renovation works presented
  • Roles and responsibilities of involved parties examined
#189 Transcript of Evidential Hearing held on 7 May 2026 (Draft)20p · ? img
fire spreadfire alarm failureresponse delayevacuation issues
  • Witnesses provided detailed accounts of fire outbreak timeline
  • Discussion on malfunctioning fire alarm systems
  • Evidence on delayed fire brigade response
  • Testimonies on building evacuation challenges
#190 Transcript of Evidential Hearing held on 8 April 2026 (Draft)50p · ? img
fire spreadfire service responsebuilding maintenancesupervision roles
  • Witness testimonies detail fire outbreak timeline
  • Fire service response times and actions reviewed
  • Building maintenance records examined
  • Issues with fire alarm activation discussed
#191 Transcript of Evidential Hearing held on 8 May 2026 (Draft)28p · ? img
fire alarm delayequipment malfunctionmaintenance lapsesemergency communication
  • Witnesses described delayed fire alarm activation
  • Fire service installations partially malfunctioned
  • Maintenance records showed irregular inspections
  • Communication breakdown among emergency responders
#192 Transcript of the Direction Conference held on 5 February 202610p · ? img
inquiry procedurecase managementevidence handlingscheduling
  • Direction conference held on 5 February 2026
  • Discussed procedural arrangements for inquiry
  • Parties agreed on timetable and document exchange
  • Clarified scope and issues for investigation
#193 Witness Statement of Ir Dr TO Chi Wing (English only)17p · 17 img
fire spreadfire service installationsbuilding maintenancesupervision gap
  • Ir Dr TO Chi Wing provided expert engineering testimony
  • Detailed analysis of fire spread mechanisms
  • Assessment of fire service installations effectiveness
  • Evaluation of building maintenance impact on fire
#194 Witness Statement of Mr CHAN Chung San (English only)8p · ? img
fire timelinefire detectionevacuation issuesequipment condition
  • Witness account of fire events at Wang Fuk Court
  • Describes timeline and fire detection
  • Notes response time of fire services
  • Mentions condition of fire safety equipment
#197 Witness Statement of Mr HAU Wa Kin (English only)13p · 13 img
contractor selectiontender processsupervision gapcompetitive bidding
  • Mr. Hau Wa Kin is Director of Prestige Construction & Engineering Co.
  • Prestige was the Registered Contractor for Wang Fuk Court renovation.
  • Mr. Ho Kin Yip, Gordon, oversaw technical and compliance aspects of projects.
  • Consultants' bidding prices were not disclosed to Prestige before appointment.
#198 Witness Statement of Mr HO Cheung Ming (English only)3p · 3 img
fire detectionevacuationfire alarm systemcommunication
  • Witness Mr Ho Cheung Ming observed fire outbreak details
  • Described initial fire detection and response actions
  • Noted issues with fire alarm activation timing
  • Provided account of evacuation procedures
#199 Witness Statement of Mr HOR Herman (English only)6p · 6 img
fire spreadsprinkler failurebuilding maintenanceemergency response
  • Witness observed fire origin near electrical panel
  • Noted delayed fire alarm activation
  • Sprinkler system appeared non-functional
  • Firefighters faced access difficulties
#200 Witness Statement of Mr HUI Kin On (English only)8p · 8 img
fire spreadinitial responsescaffolding fire
  • Mr. Hui Kin On was the initial Incident Commander at Wang Fuk Court fire.
  • Fire involved scaffolding on the exterior of Wang Cheong House with explosions.
  • Fire spread vertically along scaffolding, blocking rear exit with burning debris.
  • Initial firefighting involved deploying two water jets to control lower scaffolding fire.
#203 Witness Statement of Mr LAM Man Yan (Chinese only)8p · 1 img
fire circumstancesbuilding maintenancesupervision rolesfire service installations
  • Lam Man Yan represents Cheung Kong Property Holdings Ltd.
  • Statement submitted on March 3, 2026
  • Details on fire circumstances at Wang Fuk Court
  • Insights on building maintenance and renovation works
#204 Witness Statement of Mr LAU Fu Kwok (English only)22p · 22 img
fire spreadfire service installationsbuilding maintenanceemergency response
  • Witness account of fire events at Wang Fuk Court
  • Describes timeline and fire detection response
  • Details on fire service installations observed
  • Comments on building maintenance status
#205 Witness Statement of Mr LAW Kwok Shui (Chinese only)7p · 1 img
fire circumstancesbuilding maintenancewitness testimonyfire response
  • Witness statement by Mr. Law Kwok Shui for independent committee
  • Represents Cheung Kong Property Holdings Limited
  • Statement dated 3 March 2026
  • Related to Wang Fuk Court fire inquiry
#206 Witness Statement of Mr LEE Chun Wah (English only)3p · 3 img
fire spreadevacuationfire service responsebuilding safety
  • Witness account of fire events at Wang Fuk Court
  • Describes initial fire detection and response
  • Details on fire spread and evacuation
  • Comments on fire service arrival and actions
#207 Witness Statement of Mr LEE Kwok Hung (Chinese only)13p · 13 img
fire spreadsupervision gaptender collusionbuilding safety
  • Witness Mr. Lee Kwok Hung provided testimony on Wang Fuk Court fire.
  • Fire occurred on November 26, 2025, causing multiple fatalities.
  • Allegations of irregularities in Wang Fuk Court renovation project.
  • Concerns over fire safety during renovation, including flammable materials.
#208 Witness Statement of Mr LEE Shing Foo (Chinese only)7p · 1 img
fire spreadfire service installationsbuilding maintenanceroles and responsibilities
  • 李承富為置邦興業有限公司代表作證
  • 火災發生於大埔宏福苑
  • 證詞涵蓋火災經過及相關設備狀況
  • 描述火警初期反應及救援情況
#210 Witness Statement of Mr LIE Ngai Wa (English only)3p · 3 img
fire alarm delaysprinkler failureevacuation difficultiesbuilding maintenance
  • Witness observed fire outbreak on specific floor
  • Reported delayed fire alarm activation
  • Noted absence of sprinkler activation
  • Described evacuation challenges faced by residents
#212 Witness Statement of Mr NG Pui Kwan (Chinese only)3p · 26 img
witness testimonyfire incident detailslegal proceedings
  • Witness statement by Mr Ng Pui Kwan in Chinese
  • Document includes 3 pages and 26 images
  • Statement received on 08/01/2020
  • Involves legal counsel Lee Chi Fan
#213 Witness Statement of Mr NG Wing Kwong (English only)3p · 4 img
fire spreadfire responseequipment statuscommunication
  • Witness Mr NG Wing Kwong provides firsthand fire incident account
  • Describes fire origin and initial spread conditions
  • Details response actions taken during fire
  • Mentions fire safety equipment status
#214 Witness Statement of Mr PANG Yuk Lung, Michael (English only)70p · 1 img
fire spreadbuilding maintenancesupervision gapfire response
  • Witness statement by Mr Pang Yuk Lung, Michael
  • Details on fire incident at Wang Fuk Court
  • Observations on fire spread and response
  • Comments on building maintenance and safety measures
#216 Witness Statement of Mr TE Chi Wang (English only)13p · 13 img
fire originalarm delaysprinkler failureevacuation issues
  • Witness observed fire origin in flat 7B kitchen area
  • Reported delayed fire alarm activation
  • Noted absence of functional sprinkler system
  • Described evacuation challenges faced by residents
#217 Witness Statement of Mr TONG Hing Lun (Chinese only)4p · 11 img
witness testimonyfire circumstancesfire responseinvestigation evidence
  • Witness statement by Mr Tong Hing Lun for Wang Fuk Court fire inquiry
  • Statement includes personal identification and residence details
  • Details pertain to the fire incident in November 2025
  • Contains observations relevant to fire circumstances and response
#219 Witness Statement of Mr TSUI Moon Come (Chinese only)31p · 1 img
fire spreadfire service responsebuilding maintenancesupervision
  • Witness statement by Mr Tsui Moon Come on Wang Fuk Court fire
  • Details personal observations during the fire incident
  • Describes timeline and fire spread conditions
  • Mentions fire service response and equipment status
#220 Witness Statement of Mr WONG Chung Kee, Steve (English only)5p · 5 img
fire spreadsprinkler failureevacuation issuesemergency response
  • Witness observed fire ignition and rapid spread
  • Reported delays in fire alarm activation
  • Noted malfunction of sprinkler system on site
  • Described evacuation challenges faced by residents
#221 Witness Statement of Mr WONG Kin Wa (Chinese only)4p · 4 img
fire spreadfire system shutdownmaintenance oversightemergency response
  • Witness Wong Kin Wa employed by Hong Tai Fire Engineering Co.
  • Fire pump and alarm systems were shut off during maintenance.
  • Fire pump pipes disconnected, affecting water supply to rooftop tanks.
  • Maintenance works included emergency lighting and fire hose reel replacements.
#223 Witness Statement of Mr WONG Se King, Peter19p · 19 img
fire detectionevacuationcommunication gapsfire safety features
  • Witness Mr Wong Se King provided detailed fire incident account
  • Described timeline and fire detection response
  • Noted issues with fire alarm activation delay
  • Mentioned evacuation procedures and challenges
#224 Witness Statement of Mr YAM Lap Yin, Brian (Chinese only)3p · 3 img
fire incident accountbuilding conditionsfire safety managementurban renewal
  • Witness statement by Mr. Yam Lap Yin, Brian
  • Affiliated with Urban Renewal Authority
  • Provides firsthand account related to Wang Fuk Court fire
  • Details on building conditions and fire response
#226 Witness Statement of Mr YIM Choi Wah, Alex (English only)10p · 10 img
fire detectionemergency responsefire safety equipmentevacuation
  • Witness Alex Yim details fire incident observations
  • Describes timeline and initial fire detection
  • Notes response actions by building management
  • Mentions fire safety equipment status
#227 Witness Statement of Mr YIP Ka Kui, Sdanni (Chinese only)15p · 15 img
fire spreadconstruction materialssupervision gaptender collusion
  • Witness Yip Ka Kui's wife died in Wang Fuk Court fire.
  • Fire spread linked to construction materials and blocked windows.
  • Fire alarms in Hong Tai Court reportedly did not activate.
  • Construction workers allegedly smoked on-site despite complaints.
#229 Witness Statement of Mr YUEN Tsz Lok, Murphy (English only)19p · 19 img
fire timelineevacuationfire service responsebuilding safety
  • Witness account of fire events at Wang Fuk Court
  • Describes timeline and fire detection response
  • Details on evacuation procedures followed
  • Observations on fire service arrival and actions
#230 Witness Statement of Mr YUNG Kam Hung, Michael (English only)12p · 12 img
fire spreadfire service installationsevacuation challengessupervision gap
  • Witness account of fire events at Wang Fuk Court
  • Describes fire detection and alarm response timeline
  • Details on evacuation procedures and challenges
  • Observations on fire service installations' performance
#231 Witness Statement of Ms CHAN Hau Man (English only)13p · 13 img
fire responseevacuationfire safety equipmentbuilding maintenance
  • Witness account of fire events at Wang Fuk Court
  • Describes evacuation and fire response actions
  • Notes condition and functionality of fire safety equipment
  • Mentions communication with fire services
#233 Witness Statement of Ms CHEUNG Yuk Ching, Karen (English only)34p · 34 img
evacuationfire detectionemergency responsebuilding safety
  • Witness account of fire events at Wang Fuk Court
  • Describes evacuation procedures and challenges
  • Details on fire detection and alarm response
  • Observations on building safety features
#235 Witness Statement of Ms CHUNG Sui Ha (Chinese only)8p · 1 img
witness testimonyfire incidentcompany representationinvestigation process
  • Witness statement by Ms Chung Sui Ha for Zhihang Industrial Ltd.
  • Statement dated March 9, 2026, for Wang Fuk Court fire inquiry.
  • Provides personal address and background information.
  • Details involvement or observations related to the fire incident.
#237 Witness Statement of Ms LI Ho Ying (English only)3p · 3 img
fire originalarm delayevacuation issuesequipment maintenance
  • Witness observed fire origin near electrical panel
  • Reported delay in fire alarm activation
  • Noted absence of sprinkler activation
  • Described evacuation challenges faced by residents
#238 Witness Statement of Ms LI Ka Yuen, Sandy (English only)4p · 4 img
fire spreadalarm system failureevacuation proceduresbuilding maintenance
  • Witness Ms Li Ka Yuen present during Wang Fuk Court fire
  • Observed fire spread rapidly through common areas
  • Reported delays in fire alarm activation
  • Noted absence of clear evacuation instructions
#240 Witness Statement of Ms LO Hiu Kei (Chinese only)5p · 5 img
fire spreadbuilding maintenancefire alarm failurerenovation impact
  • Witness's mother died in Wang Fuk Court fire on 2025-11-26.
  • Mother reported smoke and fire but no fire alarm sounded.
  • Building renovations blocked windows, reducing ventilation and increasing fire risk.
  • Scaffolding outside windows stored items, adding to fire hazards.
#241 Witness Statement of Ms LOK Sin Ying (Chinese only)9p · 1 img
building maintenancesupervision rolesfire causesrenovation works
  • Witness Lok Sin Ying represents Zhipang Industrial Ltd.
  • Statement dated March 3, 2026
  • Related to Tai Po Wang Fuk Court fire inquiry
  • Details on building maintenance and renovation works
#242 Witness Statement of Ms OR Wai Yin (English only)4p · 4 img
fire alarm delaysprinkler system failureevacuation issuessmoke spread
  • Witness account of fire events at Wang Fuk Court
  • Observed delayed fire alarm activation
  • Noted absence of sprinkler activation
  • Reported unclear evacuation instructions